BRZYG - F 76 GAS OIL
- MSDS: BRZYG
- Manufacturer: CALTEX BAHRAIN
- Product Name: F 76 GAS OIL
- National Stock Number: 9140-00-873-3902
Product Identification
Product ID:F 76 GAS OIL
MSDS Date:06/26/1992
FSC:9140
NIIN:00-873-3902
MSDS Number: BRZYG
Responsible Party
US
Emergency Phone: 973-75-000-3100
Cage: KO892
Contractor
Telephone: 75-000-3100
Cage: 7X567
Ingredients
PETROLEUM OIL (NO. 2 DIESEL)
CAS: 68334-30-5
Fraction By Weight: 100% %
Hazards
LD50 LC50 Mixture:NOT GIVEN
Routes of Entry: Inhalation:YES Skin:YES Ingestion:NO
Reports of Carcinogenicity:NTP:NO IARC:NO OSHA:NO
Health Hazards Acute and Chronic:EYE IRRITATION, SLIGHT ACUTE TOXICITY
BY INGESTION, ASPIRATION HAZARD, NARCOSIS, SKIN IRRITATION. MIDDLE
DISTILLATES HAVE CAUSED SKIN CANCER IN LABORATORY ANIMALS.
Explanation of Carcinogenicity:NIOSH RECOMMENDED WHOLE DIESEL EXHAUST
BE REGARDED AS POTENTIAL OCCUPATIONAL CARCINOGEN.
Effects of Overexposure:EYE IRRITATION, GASTROINTESTINAL DISTURBANCES,
DROWSINESS, NARCOSIS, SKIN IRRITATION/BURNS/BLISTERING.
Medical Cond Aggravated by Exposure:PRE-EXISTING SKIN CONDITIONS MAY BE
AGGRAVATED BY EXPOSURE.
First Aid
First Aid:EYES: FLUSH IMMEDIATELY WITH WATER FOR 15 MINUTES WHILE
HOLDING EYELIDS OPEN. INGESTION: DO NOT INDUCE VOMITING. ASPIRATION
OF FLUID CAN CAUSE SERIOUS LUNG INJURY. GET MEDICAL ATTENTION.
INHALATION: R EMOVE TO FRESH AIR. IF BREATHING HAS STOPPED, APPLY
ARTIFICIAL RESPIRATION. CALL A PHYSICIAN. SKIN: WASH THOROUGHLY
WITH SOAP AND WATER.
Fire Fighting
Flash Point Method:PMCC
Flash Point:>140F,>60C
Autoignition Temp:Autoignition Temp Text:350C
Lower Limits:NOT GIVEN
Upper Limits:NOT GIVEN
Extinguishing Media:WATER SPRAY, DRY CHEMICAL, FOAM, CARBON DIOXIDE
Fire Fighting Procedures:WATER OR FOAM MAY CAUSE FROTHING. USE WATER TO
COOL FIRE-EXPOSED CONTAINERS.
Unusual Fire/Explosion Hazard:FULL BODY FLAME-RESISTANT CLOTHING AND/OR
TURN-OUT GEAR RECOMMENDED FOR PERSONS ATTEMPTING LEAK OR SPILL
CONTROL AND FOR FIRE FIGHTING.
Accidental Release
Spill Release Procedures:ELIMINATE ALL IGNITION SOURCES INCLUDING
INTERNAL COMBUSTION ENGINES. DEENERGIZE ELECTRICAL EQUIPMENT AND
SYSTEMS. VENTIALTE AREA. CONTAIN SPILL IF POSSIBLE. REMOVE WITH
INERT ABSORBENT.
Neutralizing Agent:NONE SPECIFIED BY MANUFACTURER.
Handling
Handling and Storage Precautions:KEEP AWAY FROM HEAT, SPARKS AND FLAME.
TRANSPORT, HANDLE AND STORE IN ACCORDANCE WITH LOCAL REGULATIONS
REGARDING COMBUSTIBLE LIQUIDS.
Other Precautions:EMPTY CONTAINER RETAIN RESIDUE AND CAN BE DANGEROUS.
DO NOT PRESSURIZE, CUT, WELD, BRAZE, SOLDER, DRILL, GRIND OR EXPOSE
SUCH CONTAINERS TO HEAT, FLAME, SPARKS, STATIC ELECTRICITY OR OTHER
SOURCES OF IGNITION. THEY MAY EXPLODE.
Exposure Controls
Respiratory Protection:IF VENTILATION DOES NOT MAINTAIN INHALATION
EXOSURES BELOW PEL (TLV), USE NIOSH/MSHA APPROVED RESPIRATOR AS PER
CURRENT 29 CFR 1910.134, INSTRUCTIONS/WARNINGS AND NIOSH RESPIRATOR
SELECTION.
Ventilation:UNDER NORMAL APPLICATIONS OF THIS PRODUCT, GENERAL DILUTION
VENTILATION IS ADEQUATE.
Protective Gloves:NEOPRENE, NITRILE, N-BUTYL RUBBER
Eye Protection:CHEMICAL SAFETY GOGGLES OR FACE SHIELD
Other Protective Equipment:WEAR IMPERVIOUS PROTECTIVE CLOTHING TO AVOID
SKIN CONTACT.
Work Hygienic Practices:WASH WITH SOAP AND WATER AFTER HANDLING PRODUCT
AND BEFORE EATING DRINKING OR SMOKING.
Supplemental Safety and Health
LOW VISCOSITY PETROLEUM MIXTURE CAN CUASE LUNG INJURY IF INGESTED AND
ASPIRATED. USE ONLY AS A FUEL.
Chemical Properties
HCC:F4
Boiling Pt:B.P. Text:392F,200C
Melt/Freeze Pt:M.P/F.P Text:NOT GIVEN
Vapor Pres:LOW
Vapor Density:NOT GIVEN
Spec Gravity:0.85
Viscosity:1.7-4.5 CST
Evaporation Rate & Reference:NOT GIVEN
Solubility in Water:NIL
Appearance and Odor:CLEAR TO AMBER COLORED LIQUID
Stability
Stability Indicator/Materials to Avoid:YES
STRONG OXIDIZING MATERIALS
Stability Condition to Avoid:NONE SPECIFIED BY MANUFACTURER.
Hazardous Decomposition Products:CARBON MONOXIDE, CARBON DIOXIDE,
HYDROCARBONS
Disposal
Waste Disposal Methods:PREVENT WASTE FROM CONTAMINATING SURROUNDING
ENVIRONMENT. DISCARD ANY PRODUCT, RESIDUE, DISPOSAL CONTAINER OR
LINER IN ACCORDANCE WITH ALL FEDERAL, STATE AND LOCAL REGULATIONS.
Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.